Fri Nov 02 04:50:44 CET 2007 Communications with UPS restored. Fri Nov 02 04:51:21 CET 2007 Power failure. Fri Nov 02 04:51:23 CET 2007 Power is back. UPS running on mains. Fri Nov 02 04:51:50 CET 2007 Power failure. Fri Nov 02 04:52:01 CET 2007 Communications with UPS restored. Fri Nov 02 04:52:01 CET 2007 Running on UPS batteries. Fri Nov 02 04:52:01 CET 2007 Mains returned. No longer on UPS batteries. Fri Nov 02 04:52:01 CET 2007 Power is back. UPS running on mains. Fri Nov 02 04:52:03 CET 2007 Power failure. Fri Nov 02 04:52:05 CET 2007 Power is back. UPS running on mains. Fri Nov 02 04:52:09 CET 2007 Power failure. Fri Nov 02 04:52:19 CET 2007 Communications with UPS restored. Fri Nov 02 04:52:19 CET 2007 Running on UPS batteries. Fri Nov 02 04:52:26 CET 2007 Communications with UPS restored. Fri Nov 02 04:52:27 CET 2007 Mains returned. No longer on UPS batteries. Fri Nov 02 04:52:27 CET 2007 Power is back. UPS running on mains. Fri Nov 02 04:52:28 CET 2007 Power failure. Fri Nov 02 04:52:30 CET 2007 Power is back. UPS running on mains.Prostě taková série několika krátkých výpadků. Přisuzoval jsem to kolísání napětí v síti a nevěnoval tomu větší pozornost, nicméně včera, když jsem byl v kanceláři, najednou UPS začla zběsile vypínat a zapínat. V podstatě taková série jako v logu výše a najednou UPS lehla a server taky. Máte někdo s něčím podobným zkušenost? Myslíte, že UPS odchází a je třeba zakoupit novou? Nevím jestli to pomůže ale ještě příkládám výpis "apcaccess status"
apcaccess status APC : 001,027,0726 DATE : Fri Nov 02 08:15:25 CET 2007 HOSTNAME : server RELEASE : 3.14.2 VERSION : 3.14.2 (15 September 2007) slackware UPSNAME : server CABLE : Custom Cable Smart MODEL : Back-UPS 500 UPSMODE : Stand Alone STARTTIME: Wed Oct 31 15:34:31 CET 2007 STATUS : ONLINE BCHARGE : 100.0 Percent TIMELEFT : 43.0 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds NUMXFERS : 43 XONBATT : Fri Nov 02 04:52:28 CET 2007 TONBATT : 0 seconds CUMONBATT: 192 seconds XOFFBATT : Fri Nov 02 04:52:30 CET 2007 STATFLAG : 0x07000008 Status Flag MANDATE : 2003-07-23 SERIALNO : BB0330013879 BATTDATE : 2003-07-23 FIRMWARE : 6.4.I USB FW: c1 APCMODEL : Back-UPS 500 END APC : Fri Nov 02 08:15:25 CET 2007Díky moc.
Stáří UPS příbližně 3-4 roky.
Jak dlouho je tam baterka? Opravdu od "BATTDATE : 2003-07-23"? S nejvetsi pravdepodobnosti uz bude po ni, zivotnost byva tak max 3 roky. Spustte kalibraci a zkontrolujte jeji stav. Jeste muzete snizit citlivost UPS, pokud uz jste to neudelal.
Ono jde o to, ze pri prepnuti na baterii, je to slusny proudovy skok (z pomaleho dobijeni na rychle vybijeni) a plne nabita baterka to pri jednom prechodu zkousne. Jenze kdyz ji to udelate vickrat za kratkou dobu, tak na ni poklesne napeti tak, ze uz nedokaze bezet ani elektronika UPSky a ta se vypne.
PS: ta baterka neni zas tak draha, moje zkusenost rika, ze vymena po 2-3 letech se vyplati.
V případě, že se jedná opravdu o problémy s kvalitou síťového napětí, mohlo by pomoci tohle:
# The ONBATTERYDELAY is the time in seconds from when a power failure # is detected until we react to it with an onbattery event. # # This means that, apccontrol will be called with the powerout argument # immediately when a power failure is detected. However, the # onbattery argument is passed to apccontrol only after the # ONBATTERYDELAY time. If you don't want to be annoyed by short # powerfailures, make sure that apccontrol powerout does nothing # i.e. comment out the wall. ONBATTERYDELAY 6
Ale řekl bych, že ve starších verzích tato direktiva nebyla, všiml jsem si toho až před pár dny.